Short answer: at least once a year for the whole electrical system, and twice a year for the critical distribution gear that carries IT load. NFPA 70B (2026 edition) sets infrared thermography at a maximum 12-month interval (Table 9.3.2) and expects shorter intervals when equipment condition warrants it. In a data center, the gear closest to the racks usually does.

For decades, NFPA 70B was a recommended practice. The 2023 edition made it a standard, written in mandatory language, and the 2026 edition (published September 2025) is the current one. That matters for three reasons:

  • It can be enforced. Authorities having jurisdiction, insurers and corporate risk teams can now point to 70B as a requirement rather than a suggestion.
  • It expects a program, not an event. 70B requires a documented electrical maintenance program, with a named owner, an equipment inventory, a condition assessment and defined intervals.
  • It ties frequency to condition. Equipment in poor condition, in a harsh environment or with a history of problems is expected to be inspected more often.

What the 2026 edition adds

The infrared interval table didn’t change: 12 months for equipment in good or average condition, 6 months for equipment in poor condition. What changed is around it:

  • Repair deadlines. Findings now come with a timeline for correction, set by severity and equipment condition (§9.4). A report that sits in a drawer no longer counts as a program.
  • Continuous monitoring can count. Permanently installed temperature monitoring may satisfy the infrared requirement for the equipment it covers (§7.4.5). For everything else, the scan is still the record.
  • A bigger program. The electrical maintenance program now has 11 required elements, up from 9, including an OT cybersecurity risk assessment.
  • Criticality can be business-based. Equipment criticality can reflect business continuity, which in a data center puts the UPS-to-rack path at the top of the list.

Why data centers scan more often than once a year

A data center runs its electrical system harder and more continuously than almost any other building type. Load is high, it changes as tenants grow, and the consequence of a failure is measured in customer SLAs. Three kinds of equipment make the strongest case for a twice-yearly scan:

EquipmentWhy it gets the shorter interval
UPS modules and battery cabinetsContinuous load, high current, connections that loosen with thermal cycling
PDUs, RPPs and STSClosest to customer racks; load shifts constantly as tenants add capacity
Overhead busway and tap-off boxesHundreds of bolted joints and plug-in connections over a long run

Switchgear, transformers, generators and paralleling gear typically stay on the annual full scan, with more frequent attention if a previous scan found a problem.

What a defensible infrared program looks like

When an auditor or insurer asks to see your program, they’re looking for evidence on four points:

  1. Coverage. A list of every component inspected, not just the ones with problems. If it isn’t on the list, nobody can prove it was scanned.
  2. Interval. Dates showing each piece of equipment was inspected within its interval.
  3. Severity and action. Each finding classed by severity, with a recommended action and a priority.
  4. Closeout. Proof that findings were repaired, ideally a re-scan under load showing the repair worked.

A single annual report covers the first three. The fourth is where most programs fall short, because the repair happens weeks later and nobody goes back to verify it.

Practical scheduling

  • Scan under real load. Infrared measures heat, and heat depends on current. Scanning at 15% load hides problems that appear at 60%. Schedule around your load profile, not just your calendar.
  • Pair the mid-year scan with maintenance windows. A scan after a UPS PM or a switchgear shutdown confirms everything came back tight.
  • Keep the same thermographer where you can. Consistent technique and familiarity with your site make year-over-year comparisons meaningful.
  • Trend, don’t just report. A connection that has risen a few degrees each year is telling you something before it ever crosses a severity threshold.

The bottom line

Annual infrared is the floor NFPA 70B sets. For the gear that carries IT load, we recommend twice a year. Either way, the documentation matters as much as the scan.