We've been inside data centers since 2009.

Hyperscale campuses, national colocation portfolios, enterprise and telecom sites. Here is what that looks like in numbers, and three programs we run today.

Of infrared thermography
30 yrs1
Of critical capacity scanned annually
1+ GW2
Components scanned
500,000+3
Infrared inspections
10,000+4
States scanned
45+5
  1. 1InfraredTeam founded in 1996. In data centers since 2009.
  2. 2Published design capacity of the data center campuses we scan each year, including planned phases. Not measured load.
  3. 3Estimate across InfraredTeam, all facility types: inspections × average components per inspection.
  4. 4Inspections performed by InfraredTeam since 1996, all facility types.
  5. 5States with at least one of our inspections, all facility types.

Inside facilities run by the biggest names in data centers

  • Equinix
  • Digital Realty
  • Compass Datacenters
  • Aligned Data Centers
  • NTT Global Data Centers
  • Flexential
  • TierPoint
  • DataBank
  • Verizon
  • T-Mobile
  • AT&T
  • ExxonMobil
  • FIS
  • Fiserv

Work performed directly and through electrical contractor partners. Logos are trademarks of their owners, shown to describe experience, not to imply endorsement.

Programs we run

Three programs, client names withheld.

Data center operators rarely allow vendors to name them. These are real programs with real numbers from our delivered reports. References are available on request once we're under NDA.

Case 01

Hyperscale developer

Three campuses, thirteen buildings, one standard

3
Campuses: DFW, Northern Virginia, Phoenix
13
Hyperscale buildings on rotation
1 wk
Per building, scheduled a year ahead

An annual energized program across a hyperscale developer's campuses in three markets. Each building is scanned in its own week under the operator's MOP, with the same report format at every site so their operations team compares buildings like for like. New buildings are added to the rotation as they come online.

Case 02

National colocation and managed services portfolio

26 sites in 16 states, every year since 2018

26
Sites across 16 states
4,094
Components scanned, 2025–26
90
Findings, 6 urgent or immediate

One thermographic standard across a national portfolio of data centers. Two of the three most severe findings in the last cycle were on cooling equipment, a compressor and a condenser water pump, not on distribution gear. That's why the scope includes mechanical as well as electrical.

Case 03

Multi-site colocation provider, Dallas

Nine years unbroken at the flagship

9 yrs
Annual scans at the downtown site
1,395
Components scanned, 2025–26
7
Urgent findings, 5 on data-floor breakers

Annual infrared across three Dallas-area facilities, with the downtown site scanned every year since 2018. Five of the seven urgent findings in the last cycle were 30A breakers feeding the data floor, the circuits closest to customer racks. Easy to miss one report at a time. Obvious across three sites.

Findings log

A few things we found in data centers this year.

A selection of Class 2–4 findings from our 2026 data center reports, imaged under live load. Site and client names are removed; the state, the asset and the fix are not.

TABLE 01 · FINDINGS LOG · 2026 DATA CENTER REPORTS · SITE NAMES REMOVED
DateStateAssetFindingClassAction
SEP 2026 TX PDU 60A branch breaker at 25.6A, failing connection 4 of 4, Immediate Clean and re-torque
SEP 2026 TX CRAH 30A feed, all three phases hot 4 of 4, Immediate Replace components
SEP 2026 TX CRAH C-phase lug hot at 15A 3 of 4, Urgent Re-crimp or replace lug
SEP 2026 TX RPP 50A branch breaker at 25.1A 3 of 4, Urgent Replace breaker
AUG 2026 TX Cooling VFD Contactor A-phase hot at 52A 4 of 4, Immediate Clean and re-torque
AUG 2026 IA Telecom panel Three 50A breakers at 19–23A 3 of 4, Urgent Replace breakers
AUG 2026 OR UPS switchboard PDU feeder breaker, A and B phases hot 2 of 4, As time permits Clean and re-torque
JUL 2026 TX Distribution panel 45A rooftop-unit breaker at 22A 3 of 4, Urgent Clean and re-torque
JUN 2026 AR Transfer switch ATS normal-source A-phase connection, ~139°F 3 of 4, Urgent Clean and re-torque
MAY 2026 VA Data hall panel 20A breaker hot at 10.5A 4 of 4, Immediate Clean and re-torque
MAY 2026 NY Cooling plant MCC Condenser water pump contactor, C-phase 309°F 4 of 4, Immediate Clean and re-torque
MAR 2026 TX Generator pit panel Two 30A breakers at 20.7A and 19.6A, 114°F 2 of 4, As time permits Replace breakers
MAR 2026 TX PDU Two 30A breakers at 22A and 20A, 142°F 3 of 4, Urgent Replace breakers
MAR 2026 TX PDU 20A breaker at 17A, 131°F 3 of 4, Urgent Redistribute load
MAR 2026 TX RPP Three 30A breakers at 5A, 110°F 2 of 4, As time permits Replace breakers
FEB 2026 WI Switchgear 250A breaker, A at 157A vs B at 114A, 115°F 2 of 4, As time permits Replace breaker, re-torque

How we count

Where these numbers come from.

Big numbers are easy to print. Here is the basis for each one, so you can judge them yourself.

30 yrs Of infrared thermography
InfraredTeam, our parent company, was founded in 1996. Our first data center and telecom inspections date to 2009.
1+ GW Of critical capacity scanned annually
Combined publicly reported design capacity of the data center campuses we scan each year, including planned phases. This is design capacity, not measured load.
500,000+ Components scanned
Estimate across InfraredTeam since 1996, all facility types: total inspections multiplied by the average number of components per inspection.
10,000+ Infrared inspections
Inspections performed by InfraredTeam since 1996, across all facility types.
45+ States scanned
States where our thermographers have performed inspections, across all facility types.